System voltage

In this diagram, if the first load is a 120V computer, what is the second load shown?
A. single phase transformer, 480/120-240V
B. 208V 3-phase motor
C. 208V heater, single phase
D. 277V discharge fluorescent lighting

AnswerC. 208V heater, single phase. Neutral to any single panel bus = 120V. A load connecting two panel buses (not neutral) is 208V single phase; between three panel buses is 208V 3-phase. Since the computer is 120V, system voltage cannot be 277/480.
ARE 4.0 exam prep: BS

Comments

Try These Too!

Building Efficiency

Convert the usable area of classrooms planned with medium efficiency level of new construction to the gross building area given the following model factors: Net Assignable Square Feet: 10,000, Space Factor: 1.5, Building Efficiency Ratio: 67%

Vapor retarders

In this section, a ceiling assembly separates the attic space above from the room interior below. If the building is located in Lewisville, Texas (hot-humid zone), where is the predicted location of condensation and what is the predicted condition of the gypsum board in this assembly? (Select 2 from the following) A. outside face of vapor retarder B. inside face of vapor retarder C. gypsum board will be wet D. gypsum board will be dry