Daylighting - EA

Successful daylighting can be achieved with an effective aperture (EA) of between 0.20 - 0.30. Which of the following provides an EA within this range?
1. 105 sf net glazing area with visible light transmittance (VLT) of 0.38, in a space whose gross exterior wall area is 150 sf
2. 100 sf net glazing area with VLT of 0.53, in a space whose gross exterior wall area is 200 sf
3. 42 sf net glazing area with VLT of 0.88, in a space whose gross exterior wall area is 140 sf

AnswerEA = VT x WWR. EA = 0.264 - 0.266 - each of these windows offers the same effective aperture within the ideal value range.

Comments

Try These Too!

Fire detection

Which of the following detector types can detect smoke or a smoldering fire that has not yet burst into flames? A. Ionization B. Rise-of-temperature C. Photoelectric D. Flame detectors

Required cooling capacity

Roughly 3 tons of cooling is being estimated for a 2,700 square foot residential building. Choose 2 locations in which this estimation can be applied. A. Rhode Island B. Ontario, Canada C. Nevada D. North Carolina Answer A and B are the best answers. As a rule of thumb, 1 ton will cool 800-1000 sf in the northern US and Canada, but only 450-700 sf in the southern US. Thus, 2700 sf divided by 900 sf per ton = 3 tons. ARE 4.0 exam prep: BS