Skip to main content

Life Safety: nightclubs

100 people perished in the 2003 Station Nightclub Fire. The National Institute of Standards and Technology conducted an investigation into the multiple factors that contributed to the disaster and the great loss of life. A central issue concerns the egress system: the nightclub was required by IBC to have 3 exits, but had 4 exits and the maximum occupant load per floor area of 585 persons was not exceeded on the night of the fire by the estimated 458 attendees of the show. What could have failed to accommodate safe discharge of the occupants?
AnswerEgress widths were not properly sized, even though the number of exits was sufficient. Also, placement and configuration at the main entrance was deficient.

ARE 4.0 exam prep: SD

Resource tip: Read more about the NIST's recommendations for nightclubs as a result of their investigation of the 2003 Station Nightclub Fire.

RLGA Technical Services (consultants) also has an excellent article on this analysis.

Comments

Try These Too!

Building Efficiency

Convert the usable area of classrooms planned with medium efficiency level of new construction to the gross building area given the following model factors: Net Assignable Square Feet: 10,000, Space Factor: 1.5, Building Efficiency Ratio: 67%

Shoring

A slurry wall is a narrow trench filled with a slurry mixture composed of bentonite clay and water, enabling it to resist pressure from the surrounding earth. What type temporary support is this? A. Bracing B. Sheeting C. Underpinning Answer B. It is a type of sheeting. ARE 4.0 exam prep: SPD

Spec coordination

In case there is a discrepancy between specifications and the drawings, which takes precedence? Answer Neither, A201 considers these - quote - complementary and what is required by one shall be binding as if required by all.- unquote. ARE 4.0 exam prep: CDS